Saturday, February 18, 2023

Quick Links:.Marathon dvr2400 manual

Looking for:

Marathon dvr2400 manual 













































   

 

Marathon dvr2400 manual.Marathon DVR2400 AVR



 

It is de- regulations and sound practices. Disconnect, lock out and tag prime viewing and access. Mounting hardware consists of six customer-sup- mover and input power supplies before installing or servicing voltage regulator.

Use a voltmeter to verify that power is off before contacting plied, 12 thread-forming screws that pass through holes in the conduit conductors. Shaft rotation produces voltage in ed torque range for the steel mounting screws is 36 to 40 inch-pounds 4.

Residual voltage is present at the generator leads and regulator connections even when to 4. Refer to Section - Specifications, for environmen- the regulator fuse is removed. Arcing could spark an Figure The front dimensions without cover. The rear dimensions with cover. Cutout and Drilling Dimensions. One 1 14 position 5. One 1 18 position 5. Electrical connections shall be made by a qualified electrician in accordance with all face connections only.

One 1 5-pin USB 2. This is applicable to P2 also. Do not bundle wiring connected to P1 and P2 together this adds more strain to the connections. Figure shows the quick disconnect terminal connections located on the rear panel of the regulator.

The chassis ground terminals 2 GND must always be connected. For longer 3. Unstable operation might be observed if the GND terminals are not distance communication please used USB booster cables connected. L1 input for single phase. E2 Generator armature — terminal T2 Phase B for 3 phase output. L2 input for single phase. E3 Generator armature — terminal T3 Phase C for 3 phase output. Jumper to E2 for single phase. Never apply a voltage to these terminals.

Observe polarity. Table Quick Connect Terminals. Two chassis grounds are avail- Generator line current is stepped down through a user-supplied CT on able on the regulator.

Secondary current 5A from that transformer is applied to P1 to chassis as close to the regulator as possible. Consult current transformer in- struction manuals for CT polarity identification and install per Figure Power input terminals are labeled 3 and 4.

Sec- The generator voltage sensing terminals are labeled E1, E2, and E3. A ondary current 5A from these transformers are applied to the P1 connec- single-phase sensing connection is obtained by connecting the phase C tor terminals labeled IB1 and IB2 and P2 connector terminals labeled IA1, sensing input to terminals E2 and E3.

Consult CT instruction manuals for polarity identification and install per Figure The field output terminals for connection to the generator exciter field are Note: All transformers must have the same CT ratio. Connector P1 Terminals.

The other two switch terminals are connected to P UP and P fault condition. USB 2. Table illustrates tion of the Load Sharing function. Refer to Section — Features and Protection for a detailed description of the Exci- tation Off function. The regulator can also be configured to accept a voltage or current to be metered on this input. Refer to Section — Features and Protection for a detailed description of the Auxiliary input function.

The burden resistor should have a three-phase voltage sensing and single-phase current sensing. The value of 0. GEN B. Note: 1. Sensing potential transformer is required if generator output voltage exceeds Volts.

Notes: 1. Analog signal input when Auxiliary is configured for control. Genset battery may be connected to keep the powered on for control and monitoring. Required for shunt operation. Required only for CAN communication. Current and voltage transformers may be installed by Regal. P1 is common for both and P2 available only on the Typical Connections to a Single-Phase Generator.

Reactive Droop is not possible in this configuration. Optional S1, S2, S4 and S5 contacts supplied by customers. Voltage transformers may be installed by Regal. Open swing cover and locate the USB mini connector on the regu- lator.

Connect USB cable from your computer to the regulator. This powers up the communication. After necessary changes are made, disconnect from the regulator. The generator may be started to verify proper operation. Electrical connections munication is powered only through USB. Shaft rotation produces voltage in as follows: generators even when no excitation is applied.

Residual voltage is a. Voltage levels may be present at the exposed components when the unit is energized. This will eliminate whenever the regulator is energized. Note: Read and understand the operation of the individual adjust- Note: USB should be capable of providing 0. HMI, power on ments before attempting any adjustments. This Note: Battery should be capable of providing 0. Perform all preliminary engine governor adjustments with the regu- is present. After initial governor adjustments are complete, shut down the prime Applying voltage larger than Vac without current in- mover.

Reinstall the 5. Start and run the generator at rated speed. The regulator may enter will indicate STBY on the display. At this time, initial adjustments can be made. If adjusting via the HMI, 3. If adjusting via the see Section — Making Settings Changes. After the initial adjustments are made, shut down the generator and reconnect the regulator leads removed in Step 3.

The generator may After the initial adjustments are made, disconnect the power source and be started and final adjustments may be performed on the regulator. The generator may be started and final adjustments may be performed on the regulator. Before following the instructions below, ensure that the generator is not spinning.

The display indicates status conditions and parameter settings. Button function descriptions are given in Table Button Description This button steps the user through a menu list of editable parameters. UP This button increases the setting level fo the parameter being adjusted. DOWN This button decreases the setting level of the parameter being adjuted. ENTER This button stores the current value of the parameter being adjusted and returns the user to the main menu list.

The display is steady-on while in EDIT mode. The display flashes while button-press inactivity. No display indicates that the regulator is operating normally, but operating no display in a sleep mode.

V This display indicates that the regulator is operating normally with excitation in AVR mode. I This display indicates that the regulator is operating normally with excitation in FCR mode.

FLSH This display indicates that the regulator is operating in field flashing mode. IDLE This display indicates that the regulator is operating normally and is in Idle mode waiting for the speed to take off.

This display indicates that the regulator is in an alarm state. During this state, the regulator continues to provide exci- AXXX where xxx indicates tation if excitation is enabled. FXXX where xxx indicates This display indicates that the regulator is in a fault state. During this state, the regulator ceases to provide excitation. The HMI will 5. The stored parameter value will flash three presses. In order to make changes to settings, follow the procedure described in items below.

This feature menu until the desired parameter is displayed see Table If no allows a shortcut to set point adjustment. Parameter changes take immediate effect. Recommended torque is 7. The header displays regula- tor status and basic administration functions. The Configuration tab permits monitoring generator performance. With this software, the user will tags. The Event Log tab allows user to access the Event Log information be able to change all of the programmable parameters.

STBY indicator. STRT indicator. It is present on all tion, Identification and Event Log tabs. Administrative Buttons 1c Regulator Status 1a The administrative buttons provide communication port settings, file ma- The header panel includes four indicators that enunciate the regulator nipulation and storing to regulator non-volatile memory.

Setup Notes: This button allows the user to change serial port communication settings. The regulator needs to be in Standby Mode to load configurations. When this button is pressed, the default factory settings for the regulator are loaded into the regulators Random Access Memory RAM. When this button is pressed, all parameter values in the regulators RAM 2.

These user settings are loaded into RAM when- Connect ever the regulator is powered up. When this button is pressed, the DVRPortal software establishes commu- nication with the regulator. Communication must be established before data can be transferred between the regulator and the DVRPortal soft- ware. If their corresponding input contacts are closed, they will show as yellow. Load When this button is pressed, the user will be given the option see Figure to choose the configuration s to load from a previously saved.

When the file is selected, all user-adjustable settings from the selected. Specifically, the panel displays line-to-line voltages, line-to-neutral voltages, line currents, real power, DC and Input Metering 2b apparent power, reactive power and power factor. The RTD panel This panel displays the measured DC values of field current and field only displays the measured temperatures of the 8 RTD channels voltage, regulator temperature, generator speed, auxiliary input voltage, additional RTD module required.

When the Generator tab is active Generator frequency, input power frequency, input power voltage and default , the values displayed correspond to the generator output termi- battery voltage only. When the Regulator tab is active, the values displayed correspond to the regulator input termi- nals secondary sides of potential and current transformers. RTD Faults and Alarms.

This function is only utilized in AVR1 or AVR3 regu- panel displays faults and alarms that are currently active on the regulator. The panel displays the voltage set point reference from the The alarms and faults can be in any of four possible states: Configurations panel with arrow keys to permit voltage adjustment up and down.

The radio button for indicator next to the corresponding condition causing the alarm. In Simulated next to the corresponding condition causing the fault. Reactive Power, a flashing indicator will appear in the metering panel that indicates this mode has been selected. The real and reactive powers are created with the that are active for the RTD thermal protections.

This tab displays OT Over simulated power factor. Enabling this condition simulates a reac- tive load on the generator. Some rounding may occur for This pull down menu selects stability settings for the chosen frame size gain values due to fixed point arithmetic. Gains for the controller are displayed with gray numbers in the panel below the pull-down menu.

Selecting the appropriate frame size chooses appropriate proportional, integral and de- rivative gain values. These gain values are not editable. Regulation Modes 3c VR Excitation 3e This panel contains a radio button for selecting the regulation mode: This panel contains a radio button for disabling or enabling excitation to the field.

See the Header regulator will regulate as if AVR3 mode were selected. Otherwise, the This panel contains a radio button for selecting the input power source regulator will regulate as if AVR3 mode were selected. This sensing mode should only be selected when using three current transformers.

This is only available on the This sensing mode should only be selected when using one current transformer in phase B. Currents for phases A and C will not be metered and power measurements will be based on the assumption phase B current flows equally in phases A and C.

This value represents the desired voltage at the regulator voltage sensing terminals, regardless of PT ratio. If the regulator sensing leads are con- Note: These fields are critical for proper regulation in droop compensation, nected midpoint-to-midpoint of a series wye configuration, the desired VAR and PF regulation modes.

For protection features like reverse power generator output voltage is twice the Regulator Voltage Set Point. This panel contains the editable fields for selecting the regulator set point for the various regulation modes and the frequency characteristics of the regulator.

This value represents the desired field current of the regulator. This feature is only available in the This determines the direction of slope variation when a 0 - 5V The generator output voltages displayed in the Generator tab of the Me- is applied to Aux Input.

Refer tering panel are equivalent to the voltages displayed in the Regulator tab to Section — Features and Protection for a detailed description of the multiplied by this value. Dynamic Slope function. This panel displays the offsets contributing to the modification of the set point for the currently selected regulation mode. Refer to Section — Features and Protection for multiplied by this value. Refer to Section — Features and Protection for a detailed description of the Auxiliary Input function.

Refer to Section — Features and Protec- Frequency. Refer to Section — Features has on the regulator set point value. Refer to Section — Features and Protection for a detailed description of the step change input functions. This refer- and Protection for a detailed description of the Auxiliary Input function. Refer to Section — Features and Protection for a de- tailed description of the Auxiliary Input function. Please refer to Section — Features and Protection to see which This panel contains three sub panels for protection settings, limit settings protections can be disabled by customers.

The state of protection features is dependent on the select- fields for configurable faults and alarms. For most applications, the default ed regulation mode. Refer as disabled as these may not be applicable for that particular regulation to Section 4 for detailed description of these protections. Most of these can be either enabled or disabled. For most applications, the default limit. Enabling the limit also enables the PID controller associated with it values of these parameters should be used.

Refer to Section — Features and Protec- tion for a detailed description of the Power Limiting feature. Refer to features and protection for further de- modes. Refer to Section — Features and Protection for a detailed tails.

If the user configures this to Active High, excitation will be disabled Current Preset 6b when the contact is Active High excitation turned OFF when contact Is These radio buttons show which preset is currently active in the These provide users the ability to set the configurations for each of the presets using these radio buttons.

Here the steps that need to be followed Notes: in order to edit the preset configurations. Place the regulator is stand-by mode 2. Presets 2 through 4 will have same settings as Preset One 1. Select the preset that you would like to edit 6b e. Navigate through various tabs and modify the configurations f. This is the speed at which the regulator transitions from Stand-by to Idle mode.

Soft Start Cut in Frequency: This is the speed at which the regulator will initiate voltage soft start. Run Cut Out Hysteresis: No. Chang- to generator. User Guide for a detailed description of these features.

Zero 0 being highest priority and Five 5 being the lowest priority. For further information, please refer to standard SAE J Note: The ECU addresses can all be assigned to the same control unit. Note: When enabling multiple message groups, care must be taken to They should only be different if the regulator needs to communicate with ensure that the regulator CAN bus is not over loaded.

Each group time and priorities can be configured through this panel. It also contains editable fields for the regulator. CSV file. This allows users to share event log data. Metering will display actual temperature though. This is only available in the Failure to do so regulations and sound practices. Residual voltage is of troubleshooting is to verify proper generator and regulator connections.

Arcing could spark an 1. Verify meter is operating properly. Failure to follow these instructions could result in 2. Check the programmable settings of the regulator are correct. Verify the speed of rotation of the generator is correct. Failure to follow these instructions could result in serious personal ulator is correct and the connections are good and insulated properly. Excessive centrifugal forces could damage the rotating fields and cause parts to be expelled Carefully perform a constant excitation test of the generator and at a high rate of speed.

Follow all applicable safety warnings and cautions while per- other applicable codes, rules or regulations and sound practices should forming this test. Continue with the following troubleshooting flow charts. Adjust generator to rated speed. Change to no adjust as yes agree with necessary. Check PT polarity. Is CT ratio correct? Correct as necessary. See Figs. Is generator Is Aux Input Type overloaded? Monitor effect of set point if Aux Input, no necessary.

Excitation check threshold and no adjust as Check Under necessary. Default Voltage threshold and adjust as value: 3. Is generator exciter OK? Is PT if used ratio Inspect exciter per generator manual correct? Is Under Frequency Knee correct? Is PT if used ratio yes frequency knee to correct value correct? Is generator running at rated speed?

Check CT polarity. Correct if necessary. Check PT no nameplates. Is generator main stator OK? Inspect exciter per generator manual. The table can be used to determine what condition is ing fault condition. Field Watch. Officer's Watch. Maple Leaf. US Army. US GOV. IDF Duvdevan. Accessories Show menu Exit menu Accessories. Brushed Steel. Seat-Belt Weave. Ballistic Nylon Straps. Spring Bars. Wrist Compasses. Weather Stations. Stopwatches Show menu Exit menu Stopwatches.

Clocks Show menu Exit menu Clocks. Desktop Clocks. Wall Clocks. Travel Clocks. Charging Clocks. Emergency Gear. Laser Pointers. Merch Show menu Exit menu Merch.

Challenge Coin. Services Show menu Exit menu Services. Authorized Dealers.

 

Marathon dvr2400 manual.Marathon DVR2400 AVR



 

Therefore, the regulator Functionality of the auxiliary input is dependent on the configuration of will regulate to Auxiliary — Off Example: A programmed power factor regulation set point of 0.

Therefore, the regulator will regulate to a power factor of In this case, the power factor has gone from a lagging to a Auxiliary — Control1 leading state. These ranges are AU-. Therefore, the regulator will regulate to a reference voltage of Vrms.

Adc field current set point. The auxiliary input scale factor is disabled in FCR mode. The auxiliary input scale factor is dis- Adc. Example: The application of a 1. Example: A field current set point of 1.

The regulator provides a reactive droop compensation feature to enable reactive load sharing during parallel generator operation. Therefore, the regula- then modifies the voltage regulation set point accordingly. A unity power factor generator load results in almost no change in gen- When in PF: erator output voltage.

A lagging power factor generator load inductive In the PF regulation mode, the application of a 4 mA to 20 mA signal cor- results in a reduction of generator output voltage. Example: A programmed power factor regulation set point of 0. The effect of droop on the set point is displayed in the set point.

The droop feature is enabled and disabled through In this case, the power factor has gone from a lagging to a leading state. When three-phase current sensing is used, The regulator provides a mode in which an auxiliary voltage of 0 to the droop function responds to the average phase current.

See Figure The regulator incorporates an adjustable soft start feature that controls the time for generator voltage to ramp to the regulation set point. The ramp rate is adjust- able from 2 to seconds default of 3 seconds. This adjustment is made through the portal and cannot be made through the HMI. The Generator Under Frequency feature is also active during Generator Soft Start and takes priority in control of the generator voltage.

Field Over- Exciter Field No 0. Rated Field Under- Total Reactive Line-line Line-line voltage Voltages. Generator P state. Configurable Protection Shutdowns Generator Under Voltage Shutdown All configurable protection features have a user-defined threshold, The Generator Under Voltage protection feature is triggered if the gener- hysteresis and timer value. By default, all these protections are enabled, ator voltage drops below the threshold.

If the threshold condition for a particular protection feature is met, an alarm is triggered. An independent timer starts at the moment the The Generator Voltage Imbalance protection feature is triggered if a voltage alarm condition is triggered. The regulator stays in alarm condition unless imbalance is detected in AVR3, VAR or PF regulation modes, imbalance the measured value recovers to above or below hysteresis value depend- difference between any single phase and the average of the three phases ing on the protection function.

The fault is triggered if the voltage imbalance condition continues and the average If the timer threshold is exceeded before the alarm condition is resolved, a voltage stays below the hysteresis level for the duration of the timer. A fault signal is displayed on the HMI and in the portal. The fault is triggered if generator re- exceeds the threshold. Generator Over Voltage Shutdown The Generator Over Voltage protection feature is triggered if the generator voltage exceeds the threshold.

The fault is triggered if the generator volt- age does not fall below the hysteresis level within the timer period. By RTD temperature exceeds the set threshold on a particular channel. If the threshold condition the duration of the timer.

These over temperature protections can be en- for a particular limiter feature is met, an indicator is triggered in the portal. The voltage set point is automatical- voltage difference between any single phase and the average of the three ly adjusted by the regulator so that generator voltage follows the selected phase is more than the percentage threshold of the voltage setpoint. If generator frequency drops below cut-out frequency, the AVR1 this protection is triggered if the voltage difference between line-line regulator will stop providing generator excitation and AC metering.

The base slope is modified Non-Configurable Shutdowns describes the details of the conditions for by the slope multiplier to achieve a desired voltage roll-off characteristic. There is no alarm for this condition — the fault and shutdown is triggered shortly after the condition is met.

It is engaged if load conditions require a field the generator by modifying voltage to maintain constant output power current larger than the limit. Under such conditions, the current is limited at the limit. The portal displays this alarm condition, no HMI indication. This limiter can be enabled or disabled in the Protection Settings Tab in portal under the Limits panel. Knee Frequency. The regulator stays in this condition 2. The regulator er expired. The regulator stays in this alarm condition until the measured latches this alarm and stays in this condition until the measured resis- temperature is below the set alarm hysteresis level.

These Pre-Alarms can tance is within the measurable range of the regulator after power cycling. The alarm is triggered if the regulator 2. The regulator The Loss of AUX Input Control Current is triggered if the measured control stays in this condition until the battery voltage recovers above the thresh- current in AUX Control Mode 2 falls below the user set threshold value old value.

This alarm can be enabled or disabled under the protection tab in the portal. Note: The battery alarm is cleared once the measured battery voltage is Note: If loss of auxiliary control current alarm is enabled and if the sensed above factory set threshold on power-up.

The regulator latches this alarm and stays in this condition until the measured resistance is within the measurable range of the regulator after power cycling. It is de- regulations and sound practices.

Disconnect, lock out and tag prime viewing and access. Mounting hardware consists of six customer-sup- mover and input power supplies before installing or servicing voltage regulator. Use a voltmeter to verify that power is off before contacting plied, 12 thread-forming screws that pass through holes in the conduit conductors.

Shaft rotation produces voltage in ed torque range for the steel mounting screws is 36 to 40 inch-pounds 4. Residual voltage is present at the generator leads and regulator connections even when to 4.

Refer to Section - Specifications, for environmen- the regulator fuse is removed. Arcing could spark an Figure The front dimensions without cover. The rear dimensions with cover. Cutout and Drilling Dimensions. One 1 14 position 5. One 1 18 position 5. Electrical connections shall be made by a qualified electrician in accordance with all face connections only.

One 1 5-pin USB 2. This is applicable to P2 also. Do not bundle wiring connected to P1 and P2 together this adds more strain to the connections. Figure shows the quick disconnect terminal connections located on the rear panel of the regulator. The chassis ground terminals 2 GND must always be connected. For longer 3. Unstable operation might be observed if the GND terminals are not distance communication please used USB booster cables connected.

L1 input for single phase. E2 Generator armature — terminal T2 Phase B for 3 phase output. L2 input for single phase. E3 Generator armature — terminal T3 Phase C for 3 phase output. Jumper to E2 for single phase. Never apply a voltage to these terminals. Observe polarity. Table Quick Connect Terminals.

Two chassis grounds are avail- Generator line current is stepped down through a user-supplied CT on able on the regulator. Secondary current 5A from that transformer is applied to P1 to chassis as close to the regulator as possible. Consult current transformer in- struction manuals for CT polarity identification and install per Figure Power input terminals are labeled 3 and 4. Sec- The generator voltage sensing terminals are labeled E1, E2, and E3.

A ondary current 5A from these transformers are applied to the P1 connec- single-phase sensing connection is obtained by connecting the phase C tor terminals labeled IB1 and IB2 and P2 connector terminals labeled IA1, sensing input to terminals E2 and E3. Consult CT instruction manuals for polarity identification and install per Figure The field output terminals for connection to the generator exciter field are Note: All transformers must have the same CT ratio.

Connector P1 Terminals. The other two switch terminals are connected to P UP and P fault condition. USB 2. Table illustrates tion of the Load Sharing function. Refer to Section — Features and Protection for a detailed description of the Exci- tation Off function.

The regulator can also be configured to accept a voltage or current to be metered on this input. Refer to Section — Features and Protection for a detailed description of the Auxiliary input function. The burden resistor should have a three-phase voltage sensing and single-phase current sensing. The value of 0. GEN B. Note: 1. Sensing potential transformer is required if generator output voltage exceeds Volts.

Notes: 1. Analog signal input when Auxiliary is configured for control. Genset battery may be connected to keep the powered on for control and monitoring. Required for shunt operation. Required only for CAN communication.

Current and voltage transformers may be installed by Regal. P1 is common for both and P2 available only on the Typical Connections to a Single-Phase Generator. Reactive Droop is not possible in this configuration. Optional S1, S2, S4 and S5 contacts supplied by customers. Voltage transformers may be installed by Regal. Open swing cover and locate the USB mini connector on the regu- lator. Connect USB cable from your computer to the regulator.

This powers up the communication. After necessary changes are made, disconnect from the regulator. The generator may be started to verify proper operation. Electrical connections munication is powered only through USB.

Shaft rotation produces voltage in as follows: generators even when no excitation is applied. Residual voltage is a. Voltage levels may be present at the exposed components when the unit is energized. This will eliminate whenever the regulator is energized. Note: Read and understand the operation of the individual adjust- Note: USB should be capable of providing 0.

HMI, power on ments before attempting any adjustments. This Note: Battery should be capable of providing 0. Perform all preliminary engine governor adjustments with the regu- is present.

After initial governor adjustments are complete, shut down the prime Applying voltage larger than Vac without current in- mover. Reinstall the 5. Start and run the generator at rated speed. The regulator may enter will indicate STBY on the display.

At this time, initial adjustments can be made. If adjusting via the HMI, 3. If adjusting via the see Section — Making Settings Changes. After the initial adjustments are made, shut down the generator and reconnect the regulator leads removed in Step 3.

The generator may After the initial adjustments are made, disconnect the power source and be started and final adjustments may be performed on the regulator. The generator may be started and final adjustments may be performed on the regulator. Before following the instructions below, ensure that the generator is not spinning.

The display indicates status conditions and parameter settings. Button function descriptions are given in Table Button Description This button steps the user through a menu list of editable parameters.

UP This button increases the setting level fo the parameter being adjusted. DOWN This button decreases the setting level of the parameter being adjuted.

ENTER This button stores the current value of the parameter being adjusted and returns the user to the main menu list. The display is steady-on while in EDIT mode. The display flashes while button-press inactivity. No display indicates that the regulator is operating normally, but operating no display in a sleep mode. V This display indicates that the regulator is operating normally with excitation in AVR mode. I This display indicates that the regulator is operating normally with excitation in FCR mode.

FLSH This display indicates that the regulator is operating in field flashing mode. IDLE This display indicates that the regulator is operating normally and is in Idle mode waiting for the speed to take off.

This display indicates that the regulator is in an alarm state. During this state, the regulator continues to provide exci- AXXX where xxx indicates tation if excitation is enabled.

FXXX where xxx indicates This display indicates that the regulator is in a fault state. During this state, the regulator ceases to provide excitation. The HMI will 5. The stored parameter value will flash three presses. In order to make changes to settings, follow the procedure described in items below.

This feature menu until the desired parameter is displayed see Table If no allows a shortcut to set point adjustment. Parameter changes take immediate effect.

Recommended torque is 7. The header displays regula- tor status and basic administration functions. The Configuration tab permits monitoring generator performance.

With this software, the user will tags. The Event Log tab allows user to access the Event Log information be able to change all of the programmable parameters. STBY indicator.

STRT indicator. It is present on all tion, Identification and Event Log tabs. Administrative Buttons 1c Regulator Status 1a The administrative buttons provide communication port settings, file ma- The header panel includes four indicators that enunciate the regulator nipulation and storing to regulator non-volatile memory.

Setup Notes: This button allows the user to change serial port communication settings. The regulator needs to be in Standby Mode to load configurations. When this button is pressed, the default factory settings for the regulator are loaded into the regulators Random Access Memory RAM.

When this button is pressed, all parameter values in the regulators RAM 2. These user settings are loaded into RAM when- Connect ever the regulator is powered up. When this button is pressed, the DVRPortal software establishes commu- nication with the regulator. Communication must be established before data can be transferred between the regulator and the DVRPortal soft- ware.

If their corresponding input contacts are closed, they will show as yellow. Load When this button is pressed, the user will be given the option see Figure to choose the configuration s to load from a previously saved. When the file is selected, all user-adjustable settings from the selected. Specifically, the panel displays line-to-line voltages, line-to-neutral voltages, line currents, real power, DC and Input Metering 2b apparent power, reactive power and power factor. The RTD panel This panel displays the measured DC values of field current and field only displays the measured temperatures of the 8 RTD channels voltage, regulator temperature, generator speed, auxiliary input voltage, additional RTD module required.

When the Generator tab is active Generator frequency, input power frequency, input power voltage and default , the values displayed correspond to the generator output termi- battery voltage only. When the Regulator tab is active, the values displayed correspond to the regulator input termi- nals secondary sides of potential and current transformers.

RTD Faults and Alarms. This function is only utilized in AVR1 or AVR3 regu- panel displays faults and alarms that are currently active on the regulator. The panel displays the voltage set point reference from the The alarms and faults can be in any of four possible states: Configurations panel with arrow keys to permit voltage adjustment up and down.

The radio button for indicator next to the corresponding condition causing the alarm. In Simulated next to the corresponding condition causing the fault. Reactive Power, a flashing indicator will appear in the metering panel that indicates this mode has been selected. The real and reactive powers are created with the that are active for the RTD thermal protections.

This tab displays OT Over simulated power factor. Enabling this condition simulates a reac- tive load on the generator. Some rounding may occur for This pull down menu selects stability settings for the chosen frame size gain values due to fixed point arithmetic. Gains for the controller are displayed with gray numbers in the panel below the pull-down menu.

Selecting the appropriate frame size chooses appropriate proportional, integral and de- rivative gain values. These gain values are not editable.

Regulation Modes 3c VR Excitation 3e This panel contains a radio button for selecting the regulation mode: This panel contains a radio button for disabling or enabling excitation to the field. See the Header regulator will regulate as if AVR3 mode were selected. Otherwise, the This panel contains a radio button for selecting the input power source regulator will regulate as if AVR3 mode were selected. This sensing mode should only be selected when using three current transformers.

This is only available on the This sensing mode should only be selected when using one current transformer in phase B. Currents for phases A and C will not be metered and power measurements will be based on the assumption phase B current flows equally in phases A and C. This value represents the desired voltage at the regulator voltage sensing terminals, regardless of PT ratio.

If the regulator sensing leads are con- Note: These fields are critical for proper regulation in droop compensation, nected midpoint-to-midpoint of a series wye configuration, the desired VAR and PF regulation modes.

For protection features like reverse power generator output voltage is twice the Regulator Voltage Set Point. This panel contains the editable fields for selecting the regulator set point for the various regulation modes and the frequency characteristics of the regulator. This value represents the desired field current of the regulator. This feature is only available in the This determines the direction of slope variation when a 0 - 5V The generator output voltages displayed in the Generator tab of the Me- is applied to Aux Input.

Refer tering panel are equivalent to the voltages displayed in the Regulator tab to Section — Features and Protection for a detailed description of the multiplied by this value. Dynamic Slope function. This panel displays the offsets contributing to the modification of the set point for the currently selected regulation mode.

Refer to Section — Features and Protection for multiplied by this value. Refer to Section — Features and Protection for a detailed description of the Auxiliary Input function. Refer to Section — Features and Protec- Frequency. Refer to Section — Features has on the regulator set point value. Refer to Section — Features and Protection for a detailed description of the step change input functions. This refer- and Protection for a detailed description of the Auxiliary Input function.

Refer to Section — Features and Protection for a de- tailed description of the Auxiliary Input function. Please refer to Section — Features and Protection to see which This panel contains three sub panels for protection settings, limit settings protections can be disabled by customers.

The state of protection features is dependent on the select- fields for configurable faults and alarms. For most applications, the default ed regulation mode. Refer as disabled as these may not be applicable for that particular regulation to Section 4 for detailed description of these protections. Ballistic Nylon Straps. Spring Bars. Wrist Compasses. Weather Stations. Stopwatches Show menu Exit menu Stopwatches.

Clocks Show menu Exit menu Clocks. Desktop Clocks. Wall Clocks. Travel Clocks. Charging Clocks. Emergency Gear. Laser Pointers. Merch Show menu Exit menu Merch. Challenge Coin. Services Show menu Exit menu Services. Authorized Dealers. Professional Discounts. About Show menu Exit menu About. Our Story. Marathon Minutes. Contact Us. Product Manual. Click Here for Product Database. No more products available for purchase.

Pair with.

   

 

Genuine Marathon DVR to replace DVRE+ [DVRKIT] :.Document Information



   

Although you should read and follow these instructions, they are not intended as a complete list of all details for installations, operation, and maintenance. If you have any questions concerning any of the procedures, or if you have a safety concern not covered by the instructions, STOP, and contact the generator manufacturer. Disconnect, lock out and tag prime mover and input power supplies before installing or servicing voltage regulator.

Use a voltmeter to verify that power is off before contacting conductors. Shaft rotation produces voltage in generators even when no excitation is applied. Residual voltage is present at the generator leads and regulator connections even when the regulator fuse is removed. Arcing could spark an explosion if exposed to battery gases, fuel vapors or other hazardous atmospheres. Excessive centrifugal forces could damage the rotating fields and cause parts to be expelled at a high rate of speed.

It is held in place by thread-forming screws module that thread into mounting holes in the face of the regulator. The front panel display annunciates regulator status and system conditions. IP10 rear with cover Weight: 3. Pulse 1c, 2a, 2b, 3A, 3B, 4 and 5a. Regal Beloit America, Inc. Regulator functions are illustrated in the block diagram of Figure Figure Simplified Block Design.

Refer to Figure E3 A-phase for CBA rotation. Voltage applied to these inputs is scaled, condi- the active operating set point to increase. P1 and P2. Current up to 5 Arms may be monitored at these terminals. These currents are scaled, conditioned and applied to the controller. Refer Keeping either contact closed will continue to increase UP or decrease. DOWN the operating set point until a limit is reached. Field Current software. This can be adjusted from Open Closed Preset2 0. Closed Open Preset3 2.

Opening the contact enables volt- Note: age droop. Opening the contact enables needs to be powered either through AC power or battery Recommended USB 2. This can be downloaded from the generator is paralleled with utility infinite bus. Use of USB hubs is not recommended for communication purposes.

By default, these are set to active low. Polarities of these contacts can be set only in Preset 1 in case of the This permits the integration of the regulator as a node on A fault output contact is provided through terminals P, P and -P1- a CAN network. The CAN communication is powered from an on-board contacts between P and P in the event of a protective shutdown.

The controller portion of the regulator includes the microprocessor and performs measurement, computation, control and communication func- Automatic Voltage Regulation Modes AVR tions. There are two automatic voltage regulation modes. AVR1 should be se- lected if the regulator is connected for single phase voltage sensing and Power Input Stage AVR3 should be selected if the regulator is connected for three phase volt- Input power is applied to terminals 3 and 4 from a PMG.

It is rectified and age sensing. In either mode, the regulator regulates the generator RMS filtered before being applied to the power amplifier and the power supply. Regulation is accomplished by sensing generator output voltage and adjusting dc output excitation current to maintain voltage at Power Supply the regulation set point.

The Droop and Under Frequency functions may ry of the regulator. The regulation set point A four-character light-emitting-diode LED display indicates various operat- is adjusted via the UP and DOWN contact inputs, the auxiliary input when ing modes, protective functions, and adjustments.

This mode can only be entered by select- chine Interface provides more information about the front panel display. This module is interfaced to the J2 connector on the regulator via a DB25 cable.

Note: If the DC voltage is removed from the auxiliary input, the op- erating set point will no longer be modified and the regulator will Example: A programmed VAR regulation set point of Therefore, the regulator Functionality of the auxiliary input is dependent on the configuration of will regulate to Auxiliary — Off Example: A programmed power factor regulation set point of 0.

Therefore, the regulator will regulate to a power factor of In this case, the power factor has gone from a lagging to a Auxiliary — Control1 leading state. These ranges are AU-. Therefore, the regulator will regulate to a reference voltage of Vrms. Adc field current set point. The auxiliary input scale factor is disabled in FCR mode. The auxiliary input scale factor is dis- Adc. Example: The application of a 1.

Example: A field current set point of 1. The regulator provides a reactive droop compensation feature to enable reactive load sharing during parallel generator operation. Therefore, the regula- then modifies the voltage regulation set point accordingly. A unity power factor generator load results in almost no change in gen- When in PF: erator output voltage.

A lagging power factor generator load inductive In the PF regulation mode, the application of a 4 mA to 20 mA signal cor- results in a reduction of generator output voltage. Example: A programmed power factor regulation set point of 0. The effect of droop on the set point is displayed in the set point. The droop feature is enabled and disabled through In this case, the power factor has gone from a lagging to a leading state.

When three-phase current sensing is used, The regulator provides a mode in which an auxiliary voltage of 0 to the droop function responds to the average phase current. See Figure The regulator incorporates an adjustable soft start feature that controls the time for generator voltage to ramp to the regulation set point.

The ramp rate is adjust- able from 2 to seconds default of 3 seconds. This adjustment is made through the portal and cannot be made through the HMI. The Generator Under Frequency feature is also active during Generator Soft Start and takes priority in control of the generator voltage.

Field Over- Exciter Field No 0. Rated Field Under- Total Reactive Line-line Line-line voltage Voltages. Generator P state. Configurable Protection Shutdowns Generator Under Voltage Shutdown All configurable protection features have a user-defined threshold, The Generator Under Voltage protection feature is triggered if the gener- hysteresis and timer value.

By default, all these protections are enabled, ator voltage drops below the threshold. If the threshold condition for a particular protection feature is met, an alarm is triggered. An independent timer starts at the moment the The Generator Voltage Imbalance protection feature is triggered if a voltage alarm condition is triggered.

The regulator stays in alarm condition unless imbalance is detected in AVR3, VAR or PF regulation modes, imbalance the measured value recovers to above or below hysteresis value depend- difference between any single phase and the average of the three phases ing on the protection function. The fault is triggered if the voltage imbalance condition continues and the average If the timer threshold is exceeded before the alarm condition is resolved, a voltage stays below the hysteresis level for the duration of the timer.

A fault signal is displayed on the HMI and in the portal. The fault is triggered if generator re- exceeds the threshold. Generator Over Voltage Shutdown The Generator Over Voltage protection feature is triggered if the generator voltage exceeds the threshold. The fault is triggered if the generator volt- age does not fall below the hysteresis level within the timer period. By RTD temperature exceeds the set threshold on a particular channel. If the threshold condition the duration of the timer.

These over temperature protections can be en- for a particular limiter feature is met, an indicator is triggered in the portal. The voltage set point is automatical- voltage difference between any single phase and the average of the three ly adjusted by the regulator so that generator voltage follows the selected phase is more than the percentage threshold of the voltage setpoint.

If generator frequency drops below cut-out frequency, the AVR1 this protection is triggered if the voltage difference between line-line regulator will stop providing generator excitation and AC metering. The base slope is modified Non-Configurable Shutdowns describes the details of the conditions for by the slope multiplier to achieve a desired voltage roll-off characteristic.

There is no alarm for this condition — the fault and shutdown is triggered shortly after the condition is met. It is engaged if load conditions require a field the generator by modifying voltage to maintain constant output power current larger than the limit. Under such conditions, the current is limited at the limit. The portal displays this alarm condition, no HMI indication. This limiter can be enabled or disabled in the Protection Settings Tab in portal under the Limits panel.

Knee Frequency. The regulator stays in this condition 2.



No comments:

Post a Comment

Quick Links:.Marathon dvr2400 manual

Looking for: Marathon dvr2400 manual  Click here to DOWNLOAD       Marathon dvr2400 manual.Marathon DVR2400 AVR   It is de- regulations...